Combustible Dust Hazard Analysis & Testing | Fauske & Associates

Combustible Dust Hazard Analysis & Testing | Fauske & Associates

Combustible Dust Hazard Analysis & Testing | Fauske & Associates

dust testing labs near me

Very often, when performing dust and explosibility testing quotes for customers, we are asked what exactly a Go/No-Go test is? While we offer a list of testing services to determine the deflagration hazards of dust samples per ASTM (American Society of Testing and Materials), OSHA (Occupational Health & Safety Administration, NFPA (National Fire Protection Agency) and UN (United Nations), knowing what this basic test is can go a long way for tackling your safety needs.

In order to “screen” for the possibility of dust explosibility in your facility, we perform a Go/No-Go Screening Test. Based on ASTM E1226, “Standard Test Method for Explosibility of Dust Clouds”, this test is an abbreviated set explosion severity method with three dust concentrations to determine if the sample is explosible. This test is generally performed with samples tested “as received” or sieved with a 40 mesh (420μm) screen and using one 5-kJ chemical igniter as the ignition source. [>100 grams (~¼ lb) of sample less than 420μm required]

In the article: “How To Collect and Ship Combustible Dust Samples For Testing”, we discuss the simple steps for getting your samples to a lab for testing. See above for our chart that depicts the outcomes for your dust tested. If your test sample is a “Yes, it explodes” then further tests can be run to determine how quickly and how severe the explosion will be (KSt/Pmax Test), followed by testing what concentration of dust in the air will cause a risk of explosion (MEC Test). Next, another test can determine if a spark will cause an explosion (MIE) test.

But, what if your Go/No-Go test result is a “no”? Well, we next look at what temperature it will take make your dust layer ignite. To find the Minimum Autoignition Temperature (MIT) of a dust cloud in the air, the MIT tests the minimum temperature that would cause your dust cloud to ignite. Next, is the LIT Test, which determines the hot-surface ignition temperature of dust layer. Finally, a Burn Rate test is conducted to determine how quickly the dust material will burn.

All of these tests start with the Go/No-Go Test. A comprehensive DHA or Process Hazards Analysis (PHA) can apply your test results to real world scenarios at your facility. Better to know wha t you are dealing with so you can plan safely! In addition, if you have a dust collector and aren’t sure what to do next, read: “Combustible Dust Made Easy”.

Here are some other tests run for dust explosibility screening:

  • Combustible Dust Hazard Screening Test – Based on VDI2263 and UN 4.1 combustion testing. This test is to determine if a dust in a pile supports self-sustaining flame propagation. [>30 grams(~1oz)of sample less than 420μm required; >300 grams (~2/3 lb) of sample less than 420μm required if testing metal dusts]
  • Go/No-Go Screening + Combustible Dust Screening Package – Both tests run in tandem as a screening package
  • Sample Characterization Test – includes determining the sample moisture content and particle size distribution [>30 grams of samples less than 420μm required]
  • “Hard-to-ignite” Explosibility Test – Tested as above but with a 400 J ignition source. [>100 grams (~¼ lb) of sample less than 420μm required]

Unless otherwise instructed, dust testing is performed on the sample as it is received (“as received”) from your facility as mentioned earlier. It may be screened to less than 420 μm (40 mesh) – OSHA’s and NFPA’s demarcation of a “dust” – to facilitate dispersion into a dust cloud. Particle size may vary widely depending on the sample. Furthermore, please note that per ASTM recommendations (and some NPFA requirements); samples should be tested at a particle size less than 75 μm and less than 5% moisture. Please note that testing materials in a method not complying with the ASTM/EU recommendations may produce explosion severity and explosion sensitivity data that is not considered conservative enough for explosion mitigation design.

This post was last modified on November 27, 2024 4:46 am